"The Sewerage of Sea Coast Towns" by Henry C. Adams is a scientific publication written during the late 19th century. This work focuses on the engineering and design principles involved in the sewerage systems of coastal towns, particularly emphasizing the unique challenges posed by tidal waters. Throughout the text, the author aims to provide practical guidance to engineers tasked with the planning and implementation of effective sewage disposal systems, with a keen attention to factors such as tides, currents, and site selection. The beginning of the book introduces the foundational principles necessary for understanding tides and currents, essential for the effective design of sewer systems in seaside environments. Adams explains how the gravitational influences of the moon and sun, along with the physical characteristics of bodies of water, directly affect the tidal movements critical to sewage discharge. The opening section further emphasizes unique considerations necessary for coastal town sewerage systems compared to inland counterparts, highlighting the complexity of marine environments and encouraging engineers to adapt their designs accordingly to ensure effective and sanitary sewage management.
Introduction adapted from the source catalogue; source summaries may be automatically generated.
Free to read · English · 35,495 words · No account needed
MAKE TIME FOR A GOOD BOOK
On by default. Untick to stop anonymous reading totals. Each page counts after 10 seconds in view. How this works.
Anonymous counting is on unless you have switched it off.
A simpler way of arriving at the size would be to calculate it by Santo Crimp's formula for sewer discharge, namely, velocity in feet per second =
[*Math: 124 \sqrt[3]{R^2} \sqrt{S}],
where R equals hydraulic mean depth in feet, and S = the ratio of fall to length; the fall being taken as the difference in level between the sewage and the sea after allowance has been made for the differing densities. In this case the fall is 20.42 ft in a length of 6,126 ft, which gives a gradient of 1 in 300. The hydraulic mean depth equals
[*Math: \frac{d}{4}];
the required discharge, 2,497 cubic feet per min, equals the
area,
[*Math: (\frac{\pi d^2}{4})]
multiplied by the velocity, therefore the velocity in feet per
second = 4/(pi d^2) x 2497/60 = 2497/(15 pi d^2) and the
formula then becomes
2497/(15 pi d^2) = 124 x * 3rdroot(d^2)/3rdroot(4^3*) x
sqrt(1)/sqrt(300)
or d^2 x 3rdroot(d^2) = 3rdroot(d^6) = (2497 x 3rd_root(16) x sqrt(300)) / (124 x 15 x 3.14159*)
or (8 x log d)/3 = log 2497 + (1/3 x log 16) + (* x log 300) -
log 124 - log 15 - log 3.14159;
or log d = 3/8 (3.397419 + 0.401373 + 1.238561 - 2.093422 - 1.176091 - 0.497150) = 3/8 (1.270690) = 0.476509.
* d = 2.9958* feet = 35.9496, say 36 inches.
As it happens, this could have been obtained direct from the tables where the discharge of a 36 in pipe at a gradient of 1 in 300 = 2,506 cubic feet per minute, as against 2,497 cubic feet required, but the above shows the method of working when the figures in the tables do not agree with those relating to the particular case in hand.
This result differs somewhat from the one previously obtained, but there remains a third method, which we can now make trial of--namely, Saph and Schoder's formula for the discharge of water mains, V = 174 3rd_root(R^2) x S^.51*. Substituting values similar to those taken previously, this formula can be written
2497/(15 pi d^2) = 174 x 3rdroot(d2)/3rd_root(4^2) x
1^.51/300^.51
or d^2 x 3rdroot(d^2) = 3rdroot(d^6) = (2497 x 3rd_root(16) x
300^.51) / (174 x 15 x 3.14159)
or* log d = 3/8 (3.397419 + 0.401373 + (54 x 2.477121) - 2.240549 - 1.176091 - 0.497150) = 3/8 (1.222647) = 0.458493
* d = 2.874* feet = 34.388 say 34 1/2 inches.
By Neville's general formula the velocity in feet per second = 140 SQRT(RS)-11(RS)^(1/3) or, assuming a diameter of 37 inches,
V = 140 X SQRT(37/(12 x 4) x 1/300) - 11 (37/(12x4x300))^(1/3)
= 140 x SQRT(37/14400) - 11 (37/1440)^(1/3)
= 7.09660 - 1.50656 = 5.59 feet per second.
Discharge = area x velocity; therefore, the discharge in cubic
feet per minute
= 5.59 x 60 x (3.14159 x 37^2)/(4*12^2) = 2504 compared with
2,497 c.f.m, required, showing that if this formula is used the
pipe should be 37 in diameter.
The four formulæ, therefore, give different results, as
follows:--
Hawksley = 40 in
Neville = 37 in
Santo Crimp = 36 in
Saph and Schoder = 34-1/2 in
The circumstances of the case would probably be met by constructing the outfall 36 in in diameter.
Your reading position is saved on this browser. Take it to another device with a library code. Reading pages adapt to text, rather than matching a printed edition.
BEHIND THE BOOK
This eBook is for the use of anyone anywhere in the United States and most other parts of the world at no cost and with almost no restrictions whatsoever. You may copy it, give it away or re-use it under the terms of the Project Gutenberg License included with this eBook or online at www.gutenberg.org. If you are not located in the United States, you will have to check the laws of the country where you are located before using this eBook. Read the source licence.
The original source file, including credits and licence, is retained by this library. Request an original-format copy at no charge. Please include the book title and Project Gutenberg identifier #7980.
KEEP YOUR CURIOSITY GOING

John Muir

Asa Gray
Asa Gray

Florence Nightingale
Elizabeth Robins Pennell
Denison Olmsted