"The Sewerage of Sea Coast Towns" by Henry C. Adams is a scientific publication written during the late 19th century. This work focuses on the engineering and design principles involved in the sewerage systems of coastal towns, particularly emphasizing the unique challenges posed by tidal waters. Throughout the text, the author aims to provide practical guidance to engineers tasked with the planning and implementation of effective sewage disposal systems, with a keen attention to factors such as tides, currents, and site selection. The beginning of the book introduces the foundational principles necessary for understanding tides and currents, essential for the effective design of sewer systems in seaside environments. Adams explains how the gravitational influences of the moon and sun, along with the physical characteristics of bodies of water, directly affect the tidal movements critical to sewage discharge. The opening section further emphasizes unique considerations necessary for coastal town sewerage systems compared to inland counterparts, highlighting the complexity of marine environments and encouraging engineers to adapt their designs accordingly to ensure effective and sanitary sewage management.
Introduction adapted from the source catalogue; source summaries may be automatically generated.
Free to read · English · 35,495 words · No account needed
MAKE TIME FOR A GOOD BOOK
On by default. Untick to stop anonymous reading totals. Each page counts after 10 seconds in view. How this works.
Anonymous counting is on unless you have switched it off.
To take a concrete example, assume that the reservoir and outfall are constructed as shown in Fig. 34, and that it is required to know the diameter of outfall pipe when the reservoir holds 1,000,000 gallons and the whole of the pumps together, including any that may be laid down to cope with any increase of the population in the future, can deliver 600,000 gallons per hour. When the reservoir is full the top water level will be 43.00 O.D., but in order to have a margin for contingencies and to allow for the loss in head due to entry of sewage into the pipe, for friction in passing around bends, and for a slight reduction in discharging capacity of the pipe by reason of incrustation, it will be desirable to take the reservoir as full, but assume that the sewage is at the level 31.00. The head of water in the sea measured above the centre of the pipe will be 21 ft, so that
[*Math: $21 \times 1/3$],
or 7 in--say, 0.58 ft--must be added to the height of high water, thus reducing the effective head from 31.00 - 10.00 = 21.00 to 20.42 ft The quantity to be discharged will be
[*Math: $\frac{1,000,000 + (3 * 600,000)}{3}$]
= 933,333 gallons per hour = 15,555 gallons per minute, or, taking 6.23 gallons equal to 1 cubic foot, the quantity equals 2,497 cubic feet per min Assume the required diameter to be 30 in, then, by Hawksley's formula, the head necessary to produce velocity =
[*Math: $\frac{Gals. per min^2}{215 \times diameter in
inches^4} = \frac{15,555^2}{215 * 30^4}$]
= 1.389 ft, and the head to overcome friction =
[*Math: $\frac{Gals. per min^2 \times Length in yards}{240 * diameter in inches^5} = \frac{15,555^2 * 2042}{240 * 30^5}]
= 84.719. Then 1.389 + 84.719 = 86.108--say, 86.11 ft; but the
acutal head is 20.42 ft, and the flow varies approximately as
the square root of the head, so that the true flow will be
about
[*Math: $15,555 * \sqrt{\frac{20.42}{86.11} = 7574.8$]
--say 7,575 gallons. But a flow of 15,555 gallons per minute is required, as it varies approximately as the fifth power of the diameter, the requisite diameter will be about
[*Math: \sqrt[5]{\frac{30^5 \times 15,555}{7575}] = 34.64
inches.
Now assume a diameter of 40 in, and repeat the calculations. Then head necessary to produce velocity
[*Math: = \frac{15,555^2}{215 \times 40^4}] = 0.044 ft, and
head to overcome friction =
[*Math: \frac{15,555^2 \times 2042}{240 \times 40^5}]
= 20.104 ft Then 0.044 + 20.104 = 20.148, say 20.15 ft, and the true flow will therefore be about
[*Math: 15,555 * \sqrt{\frac{20.42}{20.15}}]
= 15,659 gallons, and the requisite diameter about
[*Math: \sqrt[5]{\frac{40^5 * 15,555}{15,659}}]
= 39.94 inches.
When, therefore, a 30 in diameter pipe is assumed, a diameter of 34.64 in is shown to be required, and when 40 in is assumed 39.94 in is indicated.
Let a = difference between the two assumed diameters. b = increase found over lower diameter. c = decrease found under greater diameter. d = lower assumed diameter.
Then true diameter =
[*Math: d + \frac{ab}{b+c} = 30 + \frac{10 \times 4.64}{4.64+0.06} = 30 + \frac{46.4}{4.7} = 39.872],
or, say, 40 in, which equals the required diameter.
Your reading position is saved on this browser. Take it to another device with a library code. Reading pages adapt to text, rather than matching a printed edition.
BEHIND THE BOOK
This eBook is for the use of anyone anywhere in the United States and most other parts of the world at no cost and with almost no restrictions whatsoever. You may copy it, give it away or re-use it under the terms of the Project Gutenberg License included with this eBook or online at www.gutenberg.org. If you are not located in the United States, you will have to check the laws of the country where you are located before using this eBook. Read the source licence.
The original source file, including credits and licence, is retained by this library. Request an original-format copy at no charge. Please include the book title and Project Gutenberg identifier #7980.
KEEP YOUR CURIOSITY GOING

John Muir

Asa Gray
Asa Gray

Florence Nightingale
Elizabeth Robins Pennell
Denison Olmsted