"The Filtration of Public Water-Supplies" by Allen Hazen is a scientific publication written in the early 20th century. The book discusses the critical importance of filtration systems used to purify water supplies, specifically focusing on practices in the United States compared to those in densely populated European countries. It aims to stimulate interest in improving water quality and outlines established methods and necessary conditions for effective water filtration. At the start of the book, Hazen highlights the historical development of water filtration, acknowledging earlier efforts in the United States and contrasting them with successful European practices. He underscores the detrimental effects of using unfiltered water, referencing grave public health issues like cholera outbreaks. The introduction sets the stage for discussing the fundamental principles of filtration, the evolution of methods, and emphasizes the role of proper filtration systems in ensuring the health of urban populations. This opening portion establishes a foundation for a detailed examination of filtration technologies and their significance in public health and engineering, promising a comprehensive resource for those interested in environmental science and engineering practices.
Introduction adapted from the source catalogue; source summaries may be automatically generated.
Free to read · English · 99,444 words · No account needed
MAKE TIME FOR A GOOD BOOK
On by default. Untick to stop anonymous reading totals. Each page counts after 10 seconds in view. How this works.
Anonymous counting is on unless you have switched it off.
------------+----------+--------------------+----------+--------+----------- Number | | Bacteria. | | |Sulphate of of Days |Turbidity.+----------+---------+ Per cent |Per cent| Alumina Represented.| |Raw Water.|Effluent.|remaining.|removed.|used Grains | | | | | |per Gallon. ------------+----------+----------+---------+----------+--------+----------- 7 | 0.05 | 4,773 | 1713 | 35.89 | 64.11 | 0.00 2 | 0.08 | 2,785 | 850 | 30.52 | 69.48 | 0.12 4 | 0.10 | 5,109 | 726 | 14.21 | 85.79 | 0.26 2 | 0.20 | 8,713 | 214 | 2.45 | 97.55 | 0.36 8 | 0.06 | 3,224 | 112 | 3.47 | 96.53 | 0.44 19 | 0.06 | 3,488 | 123 | 3.53 | 96.47 | 0.55 11 | 0.06 | 5,673 | 154 | 2.71 | 97.29 | 0.64 10 | 0.10 | 6,100 | 112 | 1.84 | 98.16 | 0.74 8 | 0.09 | 8,647 | 148 | 1.71 | 98.29 | 0.85 5 | 0.16 | 5,645 | 142 | 2.52 | 97.48 | 0.93 13 | 0.12 | 10,397 | 200 | 1.92 | 98.08 | 1.07 10 | 0.08 | 12,778 | 121 | 0.95 | 99.05 | 1.13 13 | 0.14 | 13,397 | 164 | 1.22 | 98.78 | 1.25 19 | 0.13 | 10,462 | 160 | 1.53 | 98.47 | 1.34 10 | 0.12 | 12,851 | 107 | 0.83 | 99.17 | 1.46 4 | 0.27 | 16,015 | 77 | 0.48 | 99.52 | 1.57 7 | 0.53 | 12,262 | 191 | 1.18 | 98.82 | 1.64 4 | 0.58 | 26,950 | 347 | 1.29 | 98.71 | 1.74 5 | 0.29 | 14,570 | 86 | 0.59 | 99.41 | 1.84 3 | 0.23 | 13,833 | 153 | 1.11 | 98.89 | 1.92 19 | 0.40 | 18,222 | 92 | 0.50 | 99.50 | 2.48 5 | 0.45 | 29,300 | 1119 | 3.82 | 96.18 | 3.37 5 | 1.06 | 33,030 | 535 | 1.62 | 98.38 | 8.06 ------------+----------+----------+---------+----------+--------+-----------
SUMMARY OF RESULTS WITH JEWELL MECHANICAL FILTER, ARRANGED ACCORDING TO SULPHATE OF ALUMINA QUANTITIES.
------------+----------+----------+---------+----------+--------+----------- Number | | Bacteria. | | |Sulphate of of Days |Turbidity.+----------+---------+ Per cent |Per cent| Alumina Represented.| |Raw Water.|Effluent.|remaining.|removed.|used Grains | | | | | |per Gallon. ------------+----------+----------+---------+----------+--------+----------- 6 | 0.03 | 14,037 | 6217 | 44.29 | 55.71 | 0.00 5 | 0.07 | 4,267 | 680 | 15.93 | 84.07 | 0.24 14 | 0.06 | 2,613 | 170 | 6.50 | 93.50 | 0.35 10 | 0.06 | 2,446 | 113 | 4.62 | 95.38 | 0.44 9 | 0.11 | 7,303 | 234 | 3.20 | 96.80 | 0.55 20 | 0.09 | 6,979 | 220 | 3.15 | 96.85 | 0.65 9 | 0.08 | 5,191 | 130 | 2.50 | 97.50 | 0.75 16 | 0.12 | 8,504 | 242 | 2.84 | 97.16 | 0.83 22 | 0.16 | 8,506 | 99 | 1.16 | 98.84 | 0.96 12 | 0.11 | 11,998 | 246 | 2.05 | 97.95 | 1.05 14 | 0.18 | 18,982 | 423 | 2.23 | 97.77 | 1.16 5 | 0.14 | 13,981 | 224 | 1.60 | 98.40 | 1.23 9 | 0.27 | 19,806 | 325 | 1.64 | 98.36 | 1.34 14 | 0.27 | 16,549 | 324 | 1.96 | 98.04 | 1.45 9 | 0.29 | 12,194 | 96 | 0.79 | 99.21 | 1.54 6 | 0.25 | 13,483 | 51 | 0.38 | 99.62 | 1.65 7 | 0.53 | 24,243 | 220 | 0.91 | 99.09 | 1.72 3 | 0.90 | 20,953 | 602 | 2.88 | 97.12 | 1.90 5 | 0.43 | 25,958 | 307 | 1.19 | 98.81 | 2.19 4 | 0.84 | 21,017 | 228 | 1.09 | 98.91 | 3.71 ------------+----------+----------+---------+----------+--------+-----------
These results are shown graphically by Fig. 21.
It will be noticed by referring to the tables that as the sulphate of alumina quantities increased the turbidities increased and the numbers of bacteria increased, as well as the bacterial efficiencies. That is to say, with the less turbid waters, small sulphate of alumina quantities have been used, the numbers of bacteria in the raw water have been low, and the bacterial efficiencies have also been low. With turbid waters much larger quantities of sulphate of alumina have been used, the raw water has contained more bacteria, and the bacterial efficiencies have been higher. It may be then that the increased efficiencies with increased quantities of sulphate of alumina are not due alone to the increased sulphate of alumina, but in part also to other conditions. Thus it may be easier to remove a large percentage of bacteria from a water containing many than from a water containing only a few.
To investigate this matter and eliminate the influence of turbidity and numbers of bacteria in the raw water, the results were first classified with reference to turbidity. The results with waters having turbidities of 0.10 or less, and called for convenience turbid waters, are arranged by alum quantities as before. Afterwards the results obtained with turbidities from 0.11 to 0.50, and called for convenience muddy waters, are grouped; and finally the results with turbid water having turbidities of 0.51 and over, and called for convenience thick waters. The results thus arranged are as follows:
SUMMARY OF RESULTS WITH WARREN MECHANICAL FILTER, ARRANGED ACCORDING TO TURBIDITIES AND SULPHATE OF ALUMINA QUANTITIES.
------------+----------+--------------------+----------+--------+----------- | | | | |Sulphate of Number | | Bacteria. | Per cent |Per cent| Alumina of Days |Turbidity.+----------+---------+remaining.|removed.|used Grains Represented.| |Raw Water.|Effluent.| | |per Gallon. ------------+----------+----------+---------+----------+--------+----------- 7 | 0.05 | 4,773 | 1713 | 35.89 | 64.11 | 0.00 2 | 0.07 | 2,785 | 850 | 30.52 | 69.48 | 0.12 12 | 0.06 | 3,209 | 224 | 7.00 | 93.00 | 0.42 31 | 0.06 | 4,238 | 119 | 2.81 | 97.19 | 0.60 9 | 0.06 | 7,953 | 130 | 1.64 | 98.36 | 0.84 16 | 0.04 | 11,265 | 137 | 1.22 | 98.78 | 1.11 29 | 0.06 | 11,500 | 158 | 1.37 | 98.63 | 1.58 | | | | | | 5 | 0.17 | 8,783 | 416 | 4.73 | 95.27 | 0.36 10 | 0.16 | 6,535 | 165 | 2.54 | 97.46 | 0.85 13 | 0.19 | 13,253 | 186 | 1.40 | 98.60 | 1.13 15 | 0.22 | 10,944 | 93 | 0.85 | 99.15 | 1.36 13 | 0.29 | 14,089 | 112 | 0.80 | 99.20 | 1.73 10 | 0.35 | 18,088 | 102 | 0.57 | 99.43 | 2.38 5 | 0.29 | 25,580 | 540 | 2.11 | 97.89 | 4.30 | | | | | | 6 | 0.87 | 25,433 | 369 | 1.45 | 98.55 | 1.74 6 | 0.73 | 26,566 | 79 | 0.30 | 99.70 | 2.64 4 | 1.35 | 42,037 | 1388 | 3.30 | 96.70 | 8.16 ------------+----------+----------+---------+----------+--------+-----------
SUMMARY OF RESULTS WITH JEWELL MECHANICAL FILTER, ARRANGED ACCORDING TO TURBIDITIES AND SULPHATE OF ALUMINA QUANTITIES.
Your reading position is saved on this browser. Take it to another device with a library code. Reading pages adapt to text, rather than matching a printed edition.
BEHIND THE BOOK
This eBook is for the use of anyone anywhere in the United States and most other parts of the world at no cost and with almost no restrictions whatsoever. You may copy it, give it away or re-use it under the terms of the Project Gutenberg License included with this eBook or online at www.gutenberg.org. If you are not located in the United States, you will have to check the laws of the country where you are located before using this eBook. Read the source licence.
The original source file, including credits and licence, is retained by this library. Request an original-format copy at no charge. Please include the book title and Project Gutenberg identifier #69025.
KEEP YOUR CURIOSITY GOING

John Muir

Asa Gray
Asa Gray

Florence Nightingale
Elizabeth Robins Pennell
Denison Olmsted