Pumps and Hydraulics, Part 2 (of 2)
N. (Nehemiah) Hawkins

THE CLASSIC COLLECTION · 1914
"Hawkins Electrical Guide v. 06 (of 10)" by N. Hawkins is a technical engineering book first published in 1914. This volume is part of a groundbreaking series designed to make the complex principles of electricity accessible to ordinary readers. Notable for its extensive detailed illustrations, the guide was published by Theodore Audel & Company—a pseudonym Hawkins used to publish his own work. The book's illustrative content became foundational for decades of electrical engineering publications.
Introduction adapted from the source catalogue; source summaries may be automatically generated.
Free to read · English · 59,005 words · No account needed
MAKE TIME FOR A GOOD BOOK
On by default. Untick to stop anonymous reading totals. Each page counts after 10 seconds in view. How this works.
Anonymous counting is on unless you have switched it off.
With a three phase shell type transformer, if both the primary and secondary be delta connected, trouble in one phase will not prevent the use of the other two phases in open delta. By short circuiting both primary and secondary of the defective phase, and cutting it out of circuit the magnetic flux in that section is entirely neutralized. This cannot be done, however, with any but delta connected shell type transformers.
Where a large number of three phase transformers can be used, it is generally advisable to install three phase units, the following advantages being in their favor as compared with single phase units:
1. Require less floor space than three single phase units; 2. Weigh less than the single phase units; 3. Simpler connections, as only three primary and three secondary leads are generally brought out; 4. Transformer presents a symmetrical and compact appearance.
~Ques. What is the character of the construction of three phase
transformers?~
Ans. The three phase transformer is practically similar to that of the single phase, except that somewhat heavier and larger parts are required for the core structure.
~COMPARISON OF AIR BLAST, WATER COOLED, AND OIL COOLED TRANSFORMERS~ ======================+=======================+======================= ~Air blast type~ | ~Water cooled type~ | ~Oil cooled type~ ----------------------+-----------------------+----------------------- ~1. COST~ ----------------------+-----------------------+----------------------- ~A. First cost~ | | Necessarily more |Least expensive of all |Necessarily more expensive than the |types. |expensive than the air water cooled type of | |blast and water cooled similar rating. | |type of similar rating. | | ~B.~ | | The installation is |Being heavier than the |Being heavier than the extremely simple. |air blast type, these |air blast and water |transformers, as a |cooled type, these Moisture that may |rule, require heavier |transformers require have collected on the |apparatus for |heavier apparatus for surfaces during |installing. Both |installing. Both transportation |transformer and tank |transformer and tank or storage should be |should be thoroughly |should be thoroughly thoroughly dried out. |dried out before being |dried out before being |filled with oil. |filled with oil. | | |The oil is usually | |supplied in 50 gal. | |hermetically sealed | |steel barrels to | |minimize possibility of| |moisture during | |transportation. | ----------------------+-----------------------+----------------------- ~C. Auxiliary | | apparatus~| | A duct, or chamber, |In most cases, cooling |Do not require cooling of considerable size |water may be obtained |water or blower. is required under the |with sufficient natural| transformers in order |head. However, there | to conduct the cooling|are frequent cases in | air to them. |which it can be | |obtained only by the | A blower outfit for |use of pumps. | supplying air is | | required. |A system of piping for | |the cooling water and | |oil drainage is | |required, the cost of | |which depends, of | |course, on the station | |layout. | ~D. Maintenance~ | | An occasional |A water pumping outfit |No air or water cleaning, for which a |would possibly require |circulation to demand supply of compressed |a trifle more attention|attention. air at about 20 lb. |than a blower outfit in| pressure is |which there are no | recommended. |valves or piping. | | | The blower outfit | | requires no more care | | than any other similar| | apparatus. | | ======================+=======================+======================= ~2. FLOOR SPACE~ ----------------------+-----------------------+----------------------- Always requires space |Extra space only |Only require space for for cooling apparatus.|required when auxiliary|the transformer as no |pumping apparatus is |extra apparatus is |necessary. |necessary ======================+=======================+======================= ~3. LOCATION~ ----------------------+-----------------------+----------------------- As the transformers |Transformers are |Transformers are are open at the top |completely enclosed but|completely enclosed but they should not be |location should be such|location should be such located where there is|that no water will fall|that no water will fall much dust or dirt nor |on leads or bushings. |on leads or bushings. where water from any | | source is liable to | |The building should be fall on them. | |well ventilated. | | | |There is no auxiliary | |apparatus. The blower should be |Location of auxiliary | so situated as to |apparatus will depend | obtain clean dry air |on the station layout. | of a temperature not | | greater than 77° Fahr.| | ======================+=======================+======================= ~4. GENERAL APPEARANCE~ ----------------------+-----------------------+----------------------- Terminal leads may |Leads are brought out |Leads are brought out be located in the |of the top of the |of the top of the base and the air |transformers. |transformers. chamber may be used | | for conducting and |Water cooling pipes | distributing the |are connected at the | connecting wiring. |top in most cases. | | | The absence of | | overhead wiring aids | | in simplifying the | | appearance of the | | station. | | ======================+=======================+======================= ~5. OPERATION~ ---------------------------------------------------------------------- Equal reliability in all three types.
Your reading position is saved on this browser. Take it to another device with a library code. Reading pages adapt to text, rather than matching a printed edition.

N. (Nehemiah) Hawkins
N. (Nehemiah) Hawkins

N. (Nehemiah) Hawkins

N. (Nehemiah) Hawkins
BEHIND THE BOOK
This eBook is for the use of anyone anywhere in the United States and most other parts of the world at no cost and with almost no restrictions whatsoever. You may copy it, give it away or re-use it under the terms of the Project Gutenberg License included with this eBook or online at www.gutenberg.org. If you are not located in the United States, you will have to check the laws of the country where you are located before using this eBook. Read the source licence.
The original source file, including credits and licence, is retained by this library. Request an original-format copy at no charge. Please include the book title and Project Gutenberg identifier #49252.
KEEP YOUR CURIOSITY GOING

Charles G. (Charles Griffith) Ross
Hannah Webster Foster

Emily Lawless
Edwin Hamlin Carr

Charles De Lano Hine
Andrew Ure